DALI - KNX GATEWAY

Device working as a gateway (protocol conversion) between a DALI network and a KNX (TP) network. Mounting in distribution board on EN 60715 rail (2 modular units, each 18 mm). To be used in KNX installations for home and building automation.

DALI side
Transmission medium: shielded twisted pair , Topology: bus, star or mixed , Current absorption: max 250 mA , DALI voltage: 9,5 V ... 22,5 V (typical 16 V) , Max length cable: 300 m (section 1,5 mm²) , Max no. of DALI devices: 64 , Baud rate: 1200 bps , Max no. of DALI groups: 16 , Max no. of DALI scenarios: 16

Control of up to 64 DALI devices in up to 16 groups , broadcast function , Addressing individual, group or central , Suitable for operation in emergency lighting systems
lightscenes , Ability to read status of the DALI device via KNX (eg brightness or device error)
web interface : Web Server Integrated with ability to parameterize the Dali via browser
Compositor program for programming

MODBUS RS485 MASTER - KNX GATEWAY

Device working as a gateway (protocol conversion) between a RS485 serial network with Modbus RTU protocol and a KNX (TP) network. Master function on the Modbus RTU network. Mounting in distribution board on EN 60715 rail (4 modular units, each 18 mm). To be used in KNX installations for home and building automation.

Modbus side
Electrically insulated RS485 serial communication port, 1-way DIP switch to activate the line terminator (120 Ohm)  , Modbus master RTU (Remote Terminal Unit) communication  , Communication speed from 1200 to 115200 baud , Device addressing from 0 to 250 , Register exchange of Coil, Input, and Input , Register Holding Register type  , Reading and writing of single and multiple registers , Volatile support memory with "Modbus image" buffer of 1440 bytes

KNX side
KNX TP (twisted pair) 9600 baud communication port, electrically insulated from power supply
Volatile support memory with "image KNX" buffer of 1440 bytes

MODBUS TCP/IP MASTER - KNX GATEWAY

Device working as a gateway (protocol conversion) between an Ethernet network with Modbus RTU protocol and a KNX (TP) network. Master function on the Modbus RTU network. Mounting in distribution board on EN 60715 rail (4 modular units, each 18 mm). To be used in KNX installations for home and building automation.

Modbus side
Ethernet (IEEE 802.3) communication port, RJ45 connector, at least 5E cable category , Modbus master RTU (Remote Terminal Unit) communication , Device addressing from 0 to 250  , Register exchange of Coil, Input, and Input Register Holding Register type , Reading and writing of single and multiple registers , Volatile support memory with "Modbus image" buffer of 1440 bytes

KNX side
KNX TP (twisted pair) 9600 baud communication port, electrically insulated from power supply
Volatile support memory with "image KNX" buffer of 1440 bytes

BACnet IP SERVER - KNX GATEWAY

Device working as a gateway (protocol conversion) between a BACnet IP network on Ethernet line and a KNX (TP) network. Server function on the BACnet IP network. Mounting in distribution board on EN 60715 rail (4 modular units, each 18 mm). To be used in KNX installations for home and building automation.

BACnet side
Ethernet (IEEE 802.3) communication port, RJ45 connector, at least 5E cable category, BACnet communication , BACnet register exchange , Volatile support memory with "BACnet image" buffer of 1440 bytes

KNX side
KNX TP (twisted pair) 9600 baud communication port, electrically insulated from power supply
Volatile support memory with "image KNX" buffer of 1440 bytes

BACnet MS/TP SERVER - KNX GATEWAY

Device working as a gateway (protocol conversion) between a BACnet MS/TP (Master Slave Token Passed) network on serial RS485 line and a KNX (TP) network. Server function on the BACnet MS/TP network. Mounting in distribution board on EN 60715 rail (4 modular units, each 18 mm). To be used in KNX installations for home and building automation.

BACnet side
Electrically insulated RS485 serial communication port, 1-way DIP switch to activate the line terminator (120 Ohm)  , BACnet communication , Communication speed from 1200 to 115200 baud  , BACnet register exchange , Volatile support memory with "BACnet image" buffer of 1440 bytes

KNX side

KNX TP (twisted pair) 9600 baud communication port, electrically insulated from power supply
Volatile support memory with "image KNX" buffer of 1440 bytes

DMX - KNX GATEWAY

Device working as a gateway (protocol conversion) between a DMX network and a KNX (TP) network. Mounting in distribution board on EN 60715 rail (4 modular units, each 18 mm). To be used in KNX installations for home and building automation.

DMX side
Electrically insulated RS485 serial communication port, 1-way DIP switch to activate the line terminator (120 Ohm) 
DMX master communication , 250 kbaud communication speed  , Device addressing from 0 to 512
• byte register writing on a maximum of 512 DMX devices

KNX side
KNX TP (twisted pair) 9600 baud communication port, electrically insulated from power supply
Volatile support memory with "image KNX" buffer of 1440 bytes

M-BUS MASTER - KNX GATEWAY

Device working as a gateway (protocol conversion) between a M-Bus network and a KNX (TP) network. Master function on the M-Bus network. Mounting in distribution board on EN 60715 rail (4 modular units, each 18 mm). To be used in KNX installations for home and building automation.

The device is available in four versions:

EK-BM1-TP-20 (max. 20 M-Bus devices)
EK-BM1-TP-40 (max. 40 M-Bus devices)
EK-BM1-TP-80 (max. 80 M-Bus devices)
EK-BM1-TP-160 (max. 160 M-Bus devices)

M-Bus side
M-Bus communication port , M-Bus communication , Communication speed from 3000 to 38400 baud 
Device addressing from 1 to 250 , Reading and writing of single and multiple registers
Volatile support memory with "M-Bus image" buffer of 1440 bytes

KNX side
KNX TP (twisted pair) 9600 baud communication port, electrically insulated from power supply
Volatile support memory with "image KNX" buffer of 1440 bytes

PROFINET - KNX GATEWAY

Device working as a gateway (protocol conversion) between a PROFINET network and a KNX (TP) network. Slave function on PROFINET network. Mounting in distribution board on EN 60715 rail (4 modular units, each 18 mm). To be used in KNX installations for home and building automation.

PROFINET side
Ethernet (IEEE 802.3) communication port, RJ45 connector, at least 5E cable category, PROFINET slave communication , PROFINET register exchange , Volatile support memory with "PROFINET image" buffer of 1440 bytes

KNX side
KNX TP (twisted pair) 9600 baud communication port, electrically insulated from power supply
Volatile support memory with "image KNX" buffer of 1440 bytes